LCM 108

Manufacturer:
Intercold
Intercold products are simple and effective solutions providing a closed operating cycle for the refrigeration systems, "Standart" split-systems are reasonably priced and can successfully compete with analogous systems by leading world and domestic manufacturers.
The split-system consists of two units (indoor and outdoor) and a remote control.
Outdoor unit:
- compressor
- microchannel condenser
- blow fan
- drier filter
- dual (high and low pressure) protection switch
Indoor unit:
- evaporator
- blow fan
- tubular electric heater for evaporator defrosting
- drain pan
Separate Control box!!!
Advantages:
-
Side arrangement of the fan – protection from rain and snow
- Separate control box – easy mounting and control
- Casing made of galvanized sheet metal with polymer coating
- Optimal model range
- System components from the most reliable European manufacturers
- Availability of "winter start" options for operation at ambient temperatures:
- not less than minus 10°С,
- not less than minus 30°С.
- Availability of "cooling/heating" option to maintain required temperature by switching between "cooling" and "heating" mode
- The indoor unit's casing is made of aluminum.
Technical features
Technical features | Unit | Value |
Working temperature | ºС | from -25 to -15 |
Starting type | Direct | |
Voltage | V | 1~220 50 Hz |
Nominal power consumption | kW | 0,6 |
Nominal current | А | 3,0 |
Starting current | А | 27 |
Current max | А | 6 |
Refrigerant | R404A | |
Defrost type | Electrical | |
Defrost capacity | kW | 0,6 |
Casing material | Painted galvanized steel | |
Gross weight | kg | 72 |
Compressor | ||
Brand | Tecumseh Europe | |
Type | Hermetic | |
Model | СAJ2446Z | |
Air condenser | ||
Fan motor capacity | kW | 0,050 |
Impeller diameter | mm | 1x250 |
Air flow | m3/h | 900 |
Air cooler | ||
Casing material | Aluminium | |
Heat exchanging surface | m2 | 5 |
Fan motor capacity | kW | 0,075 |
Impeller diameter | mm | 254 |
No. of fan motors | pcs | 1 |
Air flow | m3/h | 600 |
Fin spacing | mm | 4,2 |
Stream distance | m | 7* |
Capacity table:
Temperature inside coldroom | Ambient temperature | |||
Q, W | V м3 | |||
100 мм | 80 мм | |||
-18°C | 25°C | 763 | 3,8 | 3,4 |
32°C | 661 | 3,4 | 3 | |
40°C | 510 | 3,1 | 2,7 | |
-25°C | 25°C | 461 | 2,6 | 2,3 |
32°C | 389 | 2,3 | 2 | |
40°C | 283 | 2 | 1,8 |